PRV4 Pressure Reducing Hydrant Valve - Bib Nose
The William Eagles Pressure Reducing Hydrant 2½" nominal bore landing valve manufactured in accordance with BS 5041 Part 1 for wet risers is for use on a large cross section of both onshore and offshore. They are also commonly used in other industrial/commercial applications such as wet rising mains in offices and building hospitals and hotels.
The William Eagles P.R.V is designed to maintain a safe constant outlet pressure irrespective of varying inlet pressure and is suitable for use on sites even where high or low ambient temperatures are experienced.
Type/Style:
- Integral
Max Inlet Pressure:
- 20 bar
Regulating Pressure Range:
- 4.1 - 10.3 bar [60 - 150 psi]
Inlet Sizes:
- DN40 [1½"]
- DN50 [2"]
- DN65 [2½"]
- DN80 [3"]
- DN100 [4"]
Outlet Sizes:
- DN40 [1½"]
- DN50 [2"]
- DN65 [2½"]
- 2½"
Material Options:
- LG2 (CC491K)
- LG4 (CC492K)
- SUPER DUPLEX (A995 6A)
- AL. BRONZE - BS EN 1982 CC333G (AB2)
- 254 SMO - ASTM A351 / A351M CK3MCuN
Handwheel:
- 5" cast iron 'COOLGRIP' as standard.
- 6" gunmetal available.
Finish:
Supplied in natural finish as standard. Can be supplied painted.
Accessories:
Instantaneous outlet available with plastic or gunmetal plug & 316 st.st. chain. Screwed outlets available with gunmetal cap or plug & 316 st.st. chain.